HZZDB-30 professional Safety High Voltage Cable Oscillating Wave Test System HZZDB-30

Place of Origin: Wuhan, Hubei Province
Brand Name: HZRTZ POWER
Certification: GB/T19001-2016 idt ISO 9001:2015
Model Number: HZZDB-30
Minimum Order Quantity: 1
Price: USD 1,000 - 10,000
Packaging Details: IPPC Fumigated wooden box (lSPM15)
Delivery Time: 5-7 working days
Payment Terms: T/T
Inquiry Now
Get a Quote
Specifications
Highlight Features

professional thumper test high voltage

,

professional oscillating wave test system

,

safety thumper test high voltage

Value:
Self-assessment Decision
Portability:
Handheld / Portable Design
Operating Temperature:
-10°C To 50°C
Calibration:
Factory Calibrated With Certificate
Display:
Digital LCD Screen
Voltage Range:
Up To 100kV
Product Description
HZZDB-30 Damped Oscillating Wave Test System

The HZZDB-30 is a professional-grade diagnostic system designed for high-voltage cable testing. Engineered for precision and safety, this system provides comprehensive partial discharge and dielectric loss measurement capabilities to ensure infrastructure integrity.

  • Resists high heat, humidity, and salt spray for tropical island use
  • Runs stably at −40°C, cold-proof and anti-condensation
  • IEC compliant, with complete calibration certificates provided
  • Local support: spares, on-site training, and instrument calibration

HZZDB-30 professional Safety High Voltage Cable Oscillating Wave Test System HZZDB-30


Safety & Operational Guidelines
  • High Voltage Awareness: System components carry high voltage; avoid contact during operation.
  • Site Security: Establish clear warning signs and restricted zones; ensure only authorized personnel are present.
  • Safety Control: The damping oscillation wave unit must be connected to an external safety control unit.
  • Post-Test Protocol: Discharge and ground all equipment and cables thoroughly before entering the test area.

Commercial Details
FOB Unit: Set
Packaging / Delivery: Not specified

Technical Specifications
Parameter Specification
Power Supply 220VAC ±10%, 50Hz
Max Output Voltage 30kV
Oscillation Frequency 20Hz – 300Hz
Cable Length Range 200m – 20km
Charging Current 5mA
Switch Type Laser-triggered
PD Measurement Range 1pC – 100nC
PD Sampling Rate 100MHz
Dielectric Loss Range 0.1% – 10%
Control Mode Wireless Control