HZYZ-2008 Transformer On-load Switch Tester

Place of Origin: Wuhan, Hubei Province
Brand Name: HZRTZ POWER
Certification: GB/T19001-2016 idt ISO 9001:2015
Model Number: HZYZ-2008
Minimum Order Quantity: 1
Price: USD 1,000 - 10,000
Packaging Details: IPPC Fumigated wooden box (lSPM15)
Delivery Time: 5-7 working days
Payment Terms: T/T
Inquiry Now
Get a Quote
Specifications
Highlight Features

Transformer On load Switch Tester

,

24V power transformer testing equipment

,

Transformer Switch Tester

Parameter:
Weight
Value:
7 Kilograms
Usage:
On-load Tap-changer Characteristics Test
Test Voltage Accuracy:
1%
Gas Content:
<=0.1~0.3%
Resolution:
0.1μΩ
Test Range:
1-40Ω
Capacity Range:
10~100000KVA Distribution Transformer
Product Description
Product Overview

The on-load tap changer is the only moving part connected to the transformer circuit. The HZYZ-2008 On-Load Tap Changer Tester is specifically engineered to measure the transition waveform, transition time, transition resistance values at each moment, and three-phase simultaneity of on-load tap changers in transformers.

Key Features
  • Resists high heat, humidity, and salt spray for tropical island use
  • Runs stably at -40°C, cold-proof and anti-condensation
  • IEC compliant, with complete calibration certificates provided
  • Local support available: spares, on-site training, and instrument calibration

HZYZ-2008 Transformer On-load Switch Tester

Product Attributes
FOB Unit
Set
MOQ
1
Packaging & Delivery
Not specified
Technical Specifications
Parameter Value
Output current 1.0A, 0.5A, and 0.2A
Measurement range (Resistance) 0.3Ω to 20Ω (1.0A), 5Ω to 40Ω (0.5A), 20Ω to 100Ω (0.2A)
Transition time 0 to 320ms
Open-circuit voltage 24V
Accuracy (Resistance) ±(5% reading ±0.1Ω)
Accuracy (Time) ±(0.1% reading ±0.2ms)
Sampling rate 20kHz
Storage method Local storage
External dimensions 340mm × 245mm × 210mm
Weight 7 kilograms