HZJS-III Fully Automatically Dielectric Loss Analyzer Digital Transformer Tan Delta Tester

Place of Origin: Wuhan, Hubei Province
Brand Name: HZRTZ POWER
Certification: GB/T19001-2016 idt ISO 9001:2015
Model Number: HZJS-III
Minimum Order Quantity: 1
Price: USD 1,000 - 10,000
Packaging Details: IPPC Fumigated wooden box (lSPM15)
Delivery Time: 5-7 working days
Payment Terms: T/T
Inquiry Now
Get a Quote
Specifications
Highlight Features

digital transformer tan delta tester

,

digital tan delta transformer test

Output Waveform:
Pure Sine Wave
Keywords:
Transformer Ohm Meter
Sample Rate:
10~20 KHZ
Test Principle:
Frequency Response Analyzing
Water Content:
<=5ppm
Test Object:
Below 132KV And 100MVA Power Transformer
Powersupply:
AC 220V/50Hz Or 110V/60Hz
Duty Cycle:
60mints Or Made By Order
Product Description
Product Overview

The HZJS-III Anti-interference Different Frequency Dielectric Loss Tester adopts frequency conversion power supply technology, utilizing micro-controllers and electronic technology for automatic frequency conversion, analog-to-digital conversion, and data computation. This results in strong anti-interference capability, fast testing speed, high accuracy, and easy operation.

The frequency conversion power supply uses a high-power switching power supply, outputting single frequency 45Hz–65Hz and dual frequencies 47.5Hz/52.5Hz, 45.0Hz/55.0Hz, 57.5Hz/62.5Hz, and 55.0Hz/65.0Hz pure sine waves, with automatic voltage regulation. It automatically filters out 50Hz interference, making it suitable for on-site testing in substations with high electromagnetic interference.

Key Advantages
  • Resists high heat, humidity, and salt spray for tropical island use
  • Runs stably at -40°C — cold-proof and anti-condensation
  • IEC compliant, with complete calibration certificates provided
  • Local support: spares, on-site training, and instrument calibration
HZJS-III Fully Automatically Dielectric Loss Analyzer Digital Transformer Tan Delta Tester
Product Features
  • CVT self-excitation method
  • Reverse wiring low voltage shielding and high voltage shielding
  • External voltage and CN measurement capability
  • Frequency conversion technology
  • Over-current protection function
  • Built-in standard capacitor and high voltage power supply
  • Large LCD screen display
  • Wiring diagrams in functional interfaces, greatly assisting operation with correct wiring
Product Gallery
HZJS-III fully automatic dielectric loss analyzer front view with LCD display and control panel
Technical Specifications
No. Parameter Specification Details
1 Operating Conditions -15°C to 40°C RH < 80%
2 Anti-interference Principle Frequency conversion method
3 Power Supply AC 220V ±10% Generator compatible
4 High-Voltage Output 0.5KV–10KV Adjustable in 0.1kV increments

Accuracy 2%

Maximum Current 200mA

Capacity 2000mA
5 Self-Excitation Power Supply AC 0V–50V / 15A Single frequency 45.0Hz–65Hz adjustable; dual frequency 45.0Hz/55.0Hz, 47.5Hz/52.5Hz, 55.0Hz/65.0Hz, 57.5Hz/62.5Hz
6 Resolution tgδ: 0.001% Cx: 0.001pF
7 Accuracy Δtgδ: ±(reading × 1.0% + 0.040%) ΔCx: ±(reading × 1.0% + 1.00pF)
8 Measurement Range — tgδ No limit

Measurement Range — Cx 15pF < Cx < 300nF

10KV Cx = (Cx1 + Cx2 + Cx3 + Cx4) < 60nF

5KV Cx = (Cx1 + Cx2 + Cx3 + Cx4) < 150nF

1KV Cx = (Cx1 + Cx2 + Cx3 + Cx4) < 300nF

CVT Test Cx = (Cx1 + Cx2 + Cx3 + Cx4) < 300nF
9 Storage Capacity Supports USB data storage, capable of storing 200 sets of data
10 Dimensions (Main Unit) 40cm × 29cm × 33cm

Dimensions (Accessories) 40cm × 33cm × 15cm
11 Weight (Main Unit) 25.75kg

Weight (Accessories) 33.44kg
Product Dimensions
HZJS-III dielectric loss analyzer dimensional drawing showing main unit and accessory case measurements
Frequently Asked Questions

Q1: Is your company a sales or a manufacturer?

We are an integrated trade and manufacturing company with our own factory.

Q2: If we need to customize our own brand or if there are special requirements for the built-in software of the machine, can it be customized?

Yes, we accept OEM/ODM/OBM and can customize the built-in software of the product according to the customer's special requirements.

Q3: What is the usual lead time? How long can we receive the order after placing it?

In normal circumstances, products in stock can be received within 5 to 7 days via the fastest international express. Other situations may vary depending on the quantity of products ordered, whether there are special customization requirements, and the delivery time chosen.

Q4: How can we ensure that the product will not be damaged during transportation, considering the large size of the product?

We have professional internal and external packaging to ensure the safety and stability of the products during transportation. For fragile or other special parts, we will include an extra set to ensure that the customer can use the product immediately upon receipt.

Q5: How do you handle after-sales service? What if there is a quality problem with the product or if the customer does not know how to operate it?

For quality issues that are not caused by human error, we provide a one-year warranty from the time the product is delivered, and lifetime technical support. Other after-sales issues will be addressed by our professional technical staff within 24 hours. The product comes with a user manual and an operation video.

Related Products
Send An Inquiry