HZWJF-10kVA100kV 50kv/120kv High Voltage Power Transformer Non Partial Discharge Test System

Place of Origin: Wuhan, Hubei Province
Brand Name: HZRTZ POWER
Certification: GB/T19001-2016 idt ISO 9001:2015
Model Number: HZWJF-10kVA100kV
Minimum Order Quantity: 1
Price: USD 1,000 - 10,000
Packaging Details: IPPC Fumigated wooden box (lSPM15)
Delivery Time: 15-30 working days
Payment Terms: T/T
Inquiry Now
Get a Quote
Specifications
Highlight Features

power high voltage tester

,

power high voltage test equipment

,

transformer high voltage tester

Model NO.:
HZWJF-10kVA100kV
Max Diameter Of Workpiece:
Unlimited
Mass Scope Of Workpiece:
<900kg
Type:
High Voltage Testing Machine
Maxcapacity:
<1000KN
Accuracy Grade:
1
Load Way:
Electronic Load
Loading Method:
Static Load
Product Description
Product Overview

The HZWJF-10kVA/100kV series non-partial-discharge withstand voltage test system is designed for frequency withstand voltage testing, partial discharge measurement, and related scientific research on high voltage circuit breakers, insulators, lightning arresters, switches, mutual inductors, cable accessories, high voltage coils, and other specimens.

The complete set includes an intelligent insulation test comprehensive control system, a digital correction pulse generator, an input unit, a frequency corona-free test transformer, a non-partial-discharge coupling capacitor, a non-partial-discharge protection resistor, an electric regulator, and an isolation filtering device.

Installation requirement: The equipment must be used indoors with a dedicated, high-quality grounding system. Grounding resistance should be less than 0.5Ω — the lower, the better.

HZWJF-10kVA100kV 50kv/120kv High Voltage Power Transformer Non Partial Discharge Test System

  • Resists high heat, humidity, and salt spray for tropical island use.
  • Operates stably at −40°C; cold-proof and anti-condensation.
  • IEC compliant, with complete calibration certificates provided.
  • Local support available: spare parts, on-site training, and instrument calibration.
HZWJF-10kVA 100kV non-partial-discharge high voltage withstand test system main unit
Product Classification
No Local Discharge Control Section Partial Discharge Tester Non-Local Discharge Transformers
Manual Voltage Adjustment Analog Epoxy cartridge oil type
Electric Voltage Adjustment Digital Inflatable
Industrial control machine Control Touch Screen Optional
Digital Display Industrial control machine, can be interfaced with the State Grid EIP system Optional
Digital Display PLC + Industrial computer, can be interfaced with the State Grid EIP system Optional
Selection Guide

Voltage level refers to the test article, not the transformer.

Voltage Level (Test Article) Control Section Capacity Partial Discharge Tester Boosting Section Isolation Transformer Voltage Divider Protection Resistance
12kV switches, transformers, switch cabinets, etc. 5kVA and above Optional 50kVA and above 5kVA 50kV 50kV
24kV switches, transformers, switch cabinets, etc. 10kVA and above Optional 100kVA and above 10kVA 100kV 100kV
40.5kV switches, transformers, switch cabinets, etc. 20kVA and above Optional 120kVA and above 20kVA 120kV 120kV
Technical Parameters
I. HZWJF-50/120 Non-Local Discharge Withstand Voltage Test Device
Touch screen control panel of the HZWJF-50/120 non-local discharge withstand voltage test device

The main interface of the touch screen performs the same control functions as the upper computer. The panel digitally displays the current test voltage, test current, and other necessary information. It allows manual setup of the boosting curve (rated voltage, local discharge test current, and other necessary parameters) and completes local discharge, withstand voltage, and other tests with a single key.

The panel is equipped with an emergency stop button switch. When pressed in an emergency, the system automatically breaks the main circuit switch. A power button is also provided to start the system with electricity.

The controller has an external control function, providing a start button, stop button, and test result status indicator that can be connected to the generator section. It also has reserved interfaces for external red and green indicators, which can be installed in the main loop body part.

Specifications
  1. Rated output capacity: 50kVA (non-local discharge test)
  2. Rated output voltage: 120kV (non-local discharge test)
  3. Rated output current: 0.416A (non-local discharge test)
  4. Rated input voltage: 0.38kV
  5. Short-circuit impedance: <6%
  6. Local discharge level of the complete set: <5pC at 100% rated voltage; ≤2pC at 80% rated voltage
  7. Running time: Under 100% UH and 100% IH, continuous operation is permitted for 30 minutes from ambient temperature. Under 70% UH and IH, continuous operation is permitted from ambient temperature. Transformer winding temperature rise ≤65K; transformer oil temperature rise ≤55K.
  8. Waveform distortion rate of the set: regulator input voltage waveform distortion rate <3%; complete set output voltage waveform distortion rate ≤3%
II. YDTW-50kVA/120kVA Non-Local Discharge Test Transformer
  1. Structure type: insulated shell, oil-immersed natural cooling, single unit composition
  2. Phase number: single-phase
  3. Frequency: 50Hz
  4. Rated input voltage: 0.38kV
  5. Rated input current: 131.5A
  6. Rated output voltage: 150kV
  7. Rated output current: 0.416A
  8. Rated output capacity: 50kVA
  9. Measured winding voltage ratio: 1000:1
  10. Waveform distortion rate: ≤3%
  11. Dielectric loss factor: tanδ <0.3% (90°C)
  12. Partial discharge: ≤5pC under 100% rated voltage; ≤2pC under 80% rated voltage
  13. Insulation level: 110% rated self-induced withstand voltage for 1 minute
  14. Overcurrent capacity: Effective measures (additional protective resistors, etc.) should be taken so that insulation breakdown of the test product does not damage the test transformer. Under 110% rated current for 1 minute, overcurrent should not cause thermal damage or winding deformation.
  15. Over-voltage capability: Under 110% UH (220kV) for 1 minute, over-voltage should not cause any insulation damage to the test transformer when the waveform distortion rate is ≤5%.
  16. Running time: Under 100% UH and IH, continuous operation is permitted for 60 minutes from ambient temperature. Under 70% UH and IH, continuous operation is permitted from ambient temperature. Transformer winding temperature rise ≤65K; oil surface temperature rise ≤55K.
  17. Noise level: ≤65dB
  18. Insulating oil performance: oil withstand voltage ≥60kV; water content ≤10ppm
  19. Dielectric loss (90°C): ≤0.4%
III. TYDZ-50/0.38/0~0.42 Column Regulators
  1. Phase number: single-phase
  2. Frequency: 50Hz
  3. Rated capacity: 50kVA
  4. Rated input voltage: 0.38kV
  5. Rated input current: 131.5A
  6. Rated output voltage: 0~0.42kV
  7. Rated output current: 119A
  8. Waveform distortion rate: ≤3%
  9. Starting voltage: ≤2%
  10. Short-circuit impedance: ≤8% (within 50%~100% voltage regulation)
  11. Structure form: column, dry type
  12. Short-circuit capacity: In the transient capacity state, when the test transformer output discharges through the protective resistor onto the test piece, the short-circuit current can reach up to 2 times the output. A discharge duration of 8 cycles should not cause any thermal damage or mechanical deformation to the regulator winding.
  13. Voltage regulating method: electric voltage regulating, using DC motor drive
  14. Regulator with upper and lower limit devices
  15. Running time: same as transformer
Frequently Asked Questions

Q1: Is your company a sales agent or a manufacturer?

We are an integrated trade and manufacturing company with our own factory.

Q2: If we need to customize our own brand or have special requirements for the built-in software, can it be customized?

Yes, we accept OEM/ODM/OBM and can customize the built-in software of the product according to the customer's special requirements.

Q3: What is the usual lead time? How long until we receive the order after placing it?

In normal circumstances, products in stock can be received within 5 to 7 days via the fastest international express. Other situations may vary depending on the quantity ordered, whether there are special customization requirements, and the delivery time chosen.

Q4: Considering the large size of the product, how can we ensure it will not be damaged during transportation?

We use professional internal and external packaging to ensure the safety and stability of the products during transportation. For fragile or other special parts, we include an extra set so the customer can use the product immediately upon receipt.

Q5: How do you handle after-sales service? What if there is a quality problem or the customer does not know how to operate the product?

For quality issues not caused by human error, we provide a one-year warranty from the time the product is delivered, plus lifetime technical support. Other after-sales issues are addressed by our professional technical staff within 24 hours. The product comes with a user manual and an operation video.